Load Banks & Test Resistors for Generator/UPS Testing
Load banks apply controlled electrical load to generators (diesel, gas, hydrogen-ready), UPS systems and data-center power chains to verify performance under realistic conditions. NFPA 110 §8.4 mandates monthly 30-minute exercise of standby generators at ≥30% rated load — a load bank lets data centers run this test without dumping the load on production circuits. Hongyi supplies portable resistive load banks from 50 kW to 2.5 MW (single-trailer 800 kW typical) and stationary cabinets to 5 MW, with 1-step or stepped switching from 5% to 100% load. Voltage ratings 208 V to 13.8 kV, 50/60 Hz. Built per IEEE 115, IEC 60034-2-1 acceptance test methodologies. Cooling is forced-air (axial fans on top, ambient discharge); 0.95–1.0 power factor depending on R-only or R-L blend. Used by Cummins, Caterpillar, Kohler, Vertiv, Schneider field service teams worldwide.
Key Requirements
- Power range 50 kW–5 MW per cabinet/trailer; modular for higher totals
- Voltage ratings 208 V / 415 V / 480 V / 690 V / 4.16 kV / 6.6 kV / 11 kV / 13.8 kV per IEC 60038
- Stepped switching: 5%, 10%, 25% load increments + master ON/OFF + emergency stop
- Continuous duty (S1) per IEC 60034-1 — must run hours, not pulses
- Forced-air cooling with 70 dB(A) at 1 m, ambient -20°C to +50°C operation
- Built-in metering (kW, kVA, V, A, Hz, PF) and Modbus/RS-485 for SCADA logging
How to Select
- Match the highest generator/UPS rating you'll test, then add 25% margin (test transient overload)
- Pick voltage class one step above your equipment (480 V test → 600 V-rated load bank)
- Choose stepped resolution that resolves your acceptance criteria (typically 5% steps)
- For monthly NFPA 110 testing, prefer resistive-only (PF=1) — simpler, no kVAR variability
- For real-load simulation in data centers, choose RL load bank (PF=0.8 lag) to match server profile
- If outdoor or trailer-mount, specify NEMA 3R / IP55 enclosure with hinged panels for service
Recommended Products

Resistor Boxes
Integrated resistor cabinet solutions for industrial braking and energy dissipation
View product family
High-Power Resistors
Industrial-grade braking and discharge solutions covering 50W ~ 100kW
View product family
Aluminum Housed Resistors
Aluminum-housed resistors with superior heat dissipation — ideal for inverters, servo drives and other high-power applications
View product familyRelated Articles

How to Choose a High-Power Braking Resistor — A 2026 Engineer's Guide
Five common sizing mistakes, the formulas you actually need (with worked example), and how to read derating curves correctly.
Read article
Aluminum Housed vs Cement vs Wirewound Resistors — Complete Comparison
Which family fits your application? A 12-parameter table, decision flowchart, and three real-world case studies.
Read articleFrequently asked questions
How big a load bank do I need to test a 2 MW diesel generator?
What's the difference between a resistive-only and a resistive-reactive load bank?
Can the load bank be controlled remotely from a SCADA or laptop?
How is heat from a 2 MW load bank discharged safely?
Sample Request
Standard samples are provided free of charge in reasonable quantities (shipped within 2–3 business days). Custom samples are delivered within 2–4 weeks. Please use the form on the right to tell us:
- Company and contact details
- Target part number or key specs (power / resistance / package)
- Application scenario and estimated annual volume
- Shipping address and expected delivery date